MCG SURGE PROTECTOR SELECTION
GUIDE (MATRIX) • WWW.MCGSURGE.COM •
800-851-1508 • info1@mcgsurge.com
Revision 05/2008
Click here for a PDF Printable
version
|
Select Model for Info > |
560LS |
402XT |
300LS |
202XT |
200LS |
160MXT |
160M
■ |
150M
♣ |
125M
♣ |
120LS |
120M
■ |
90M
♣ |
PT250
♣ |
PT160 |
PT160D |
PT120
♣ |
PT80
¹ |
PT40 ¹ |
|
Amps/Phase |
560,000 |
400,000 |
300,000 |
200,000 |
200,000 |
160,000 |
160,000 |
160,000 |
120,000 |
120,000 |
120,000 |
80,000 |
250,000 |
160,000 |
160,000 |
120,000 |
80,000 |
40,000 |
|
NEMA LS1 |
● |
● |
● |
● |
● |
● |
|
|
|
● |
|
|
|
|
|
|
|
|
|
True Redundancy (Per Phase) |
14x |
10x |
7x |
5x |
5x |
4x |
2x |
2x |
2x |
3x |
2x |
2x |
3x |
2x |
2x |
2x |
|
|
|
MicroZ Cable |
Opt. |
● |
Opt. |
● |
Opt. |
● |
● |
Opt. |
Opt. |
|
|
Opt. |
|
|
|
|
|
|
|
Modular ▲ |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
|
|
|
|
|
|
|
Surge Event Counter |
Opt. |
● |
Opt. |
● |
Opt. |
● |
● |
Opt. |
Opt. |
Opt. |
● |
Opt. |
|
|
|
|
|
|
|
Date & Time last event |
|
● |
|
● |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Dry Contacts for Remote
Alarm |
Opt. |
● |
Opt. |
● |
Opt. |
● |
● |
● |
● |
Opt. |
● |
● |
● |
● |
● |
● |
● |
● |
|
Audible Alarm |
Opt. |
● |
Opt. |
● |
Opt. |
● |
● |
Opt. |
Opt. |
Opt. |
● |
Opt. |
|
|
|
|
|
|
|
Filtering |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
|
Integral Disconnect |
Opt. |
● |
Opt. |
● |
Opt. |
|
● |
|
|
Opt. |
● |
|
|
|
|
|
|
|
|
NEMA 12 |
|
|
|
|
|
|
|
● |
● |
|
|
● |
|
|
|
|
|
|
|
NEMA 4 (optional NEMA 4X SS) |
● |
● |
● |
● |
● |
● |
● |
|
|
● |
● |
|
|
|
|
|
|
|
|
Nema 1 |
|
|
|
|
|
|
|
|
|
|
|
|
● |
● |
● |
● |
● |
● |
|
Standard Cable |
|
|
|
|
|
|
|
● |
● |
|
|
● |
● |
● |
● |
● |
● |
● |
|
Required Circuit Breaker |
30A ! |
30A |
30A ! |
30A |
30A ! |
30A |
30A |
20A/30A |
20A/30A |
30A ! |
30A |
20A/30A |
30A |
30A |
30A |
30A |
30A |
30A |
|
UL-1449 2nd Edition |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
● |
|
(Including the requirements
of February 9, 2007) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Notes:
|
|
▲ LS Models - Bolt-On
Modules with internal redundant fusing and high speed integral thermal
fusing. |
• 30A max circuit
breaker for µZ cable option only. (Models 150M/125M/90M)
|
|
▲ XT Models - Bolt-On
Modules with internal redundant fusing and thermal disconnects. |
!
30A max Circuit Breaker for 10AWG µZ cable option.
|
|
▲ M Models - Plug-In Modules
with external redundant fusing. |
!
50A max Circuit Breaker for 8AWG µZ cable option.
|
|
▲ All modules and fuses have
a lifetime warranty replacement. |
! (If no cable is
ordered then follow installation manual for recommended circuit
breaker)
|
|
♣ Models are not available
in Delta Configuration. |
¹ Pending release,
June 2008 with the new UL 1449 including Feb 9,2007 Requirements.
|
|
■ Models are not available
in 600V Delta Configuration. |
|
|